Application
Oil is then pumped through a vacuum breaking valve into the degassing section where it is dehydrated and degassed. Treated oil is then pumped back to the transformer by the outlet pump. After a given period, sorbent in the back section of the equipment achieves full saturation and is no longer able to regenerate oil. At this stage, the sorbent needs to be reactivated (restored to its original state) to be able to regenerate oil again. Reactivation stage starts by draining the columns in the back section of saturated oil. After the oil has been drained, a vacuum is created and maintained throughout the whole reactivation process in the back section. Then by selective use of heating elements on the top parts of individual columns, the reactivation process is initiated. During the process, the impurities are removed from the sorbent which restores it to its original state. This entire process can be repeated many times until the sorbent starts to lose its properties and needs to be replaced.
Technical characteristics
● Unique reactivation technology.
● Automated operation on online and offline transformers.
● Automatic removal of corrosive sulfur from transformer oils.
● Works on all types of mineral transformer oils
Oil regeneration equipment is sophisticated. Its inlet pump is a positive displacement rotary pump. The outlet pump is a centrifugal closed coupled high suction pump. For degassing the rotary vane, a vacuum pump and vacuum booster roots pump are used. For the reactivation phase, a rotary piston roots pump is used. All valves across the equipment are automatic ball valves, which are pneumatically controlled. Equipment is fully automatic, controlled by PLC logic and interfaced with a SCADA system. Numerous safety features are introduced throughout the unit to ensure the safety of the equipment as well as the operating personal. Aeration valves, overheating protection, and automatic level switches guarantee the safety of the equipment as well as its ability to identify a possible risk and to power down to prevent any accidents.
Performance Values
After Treatment Parameters
Items |
Unit |
After Treatment Index |
Testing method |
Mechanical impurities |
% |
No |
GB/T511 |
Dielectric dissipation factor at 90℃ |
/ |
0.0008 |
IEC60422 |
Water Content |
Mg/L |
≤5PPM |
GB/T7600 |
Acid value |
mgkoH/g |
≤0.010 |
GB/T264 |
Cleanness |
Grade |
6 |
NAS 1638 |
Breakdown voltage value |
kV |
≥75 |
GB、DL Or IEC Standard |
Interfacial Tension |
mN/m |
49 |
IEC60422C |
Acetylene |
Mg/L |
0 |
The gas content measurement according to the standard of GB, DL and IEC |
Filter precision |
1-5um |
Oil Comparision